Call 08046054497 68% Response Rate

Send Enquiry

our range

Siemens Hmi

Offering you a complete choice of products which include gt2715-xtba mitsubishi hmi.

GT2715-XTBA Mitsubishi hmi

  • GT2715-XTBA Mitsubishi hmi
  • GT2715-XTBA Mitsubishi hmi
  • GT2715-XTBA Mitsubishi hmi
  • GT2715-XTBA Mitsubishi hmi
GT2715-XTBA Mitsubishi hmi
Get Best Quote
Rs 13,108  / PiecePrice on Request
Mounting TypePanel Mount
Screen size15 inch
Model Name/NumberGT2715-XTBA
Display Size15 inch
BrandMITSUBISHI
PhaseSingle Phase
Resolution1024 x 768 Pixels
Control TypeTouch Screen
General specifications
ItemSpecifications
Operating ambient temperature *1 0 ℃ to 55 ℃ *6 (horizontal installation), 0 ℃ to 50 ℃ (vertical installation)
Storage ambient temperature -20 ℃ to 60 ℃
Operating ambient humidity 10% RH to 90% RH, non-condensing *2
Storage ambient humidity 10% RH to 90% RH, non-condensing *2
Vibration resistance Compliant with
JIS B 3502 and
IEC 61131-2 *7
  Frequency Acceleration Half amplitude Sweep count
Under intermittent vibration 5 to 8.4 Hz - 3.5 mm 10 times in each
X, Y, or Z direction
8.4 to 150 Hz 9.8 m/s² -
Under continuous vibration 5 to 8.4 Hz - 1.75 mm -
8.4 to 150 Hz 4.9 m/s² -
Shock resistance Compliant with JIS B 3502 and IEC 61131-2 (147 m/s² (15G), 3 times in each X, Y, or Z direction) *7
Operating atmosphere No greasy fumes, corrosive gas, flammable gas, excessive conductive dust,
and direct sunlight (as well as at storage)
Operating altitude *3 2000 m or less
Installation location Inside control panel
Overvoltage category *4 Ⅱ or less
Pollution degree *5 2 or less
Cooling method Self-cooling
Grounding Grounding with a ground resistance of 100 Ω or less by using a ground cable that has a cross-sectional area of 2 mm² or more. If impossible, connect the ground cable to the control panel.
  • *1Includes the temperature inside the enclosure of the control panel to which the GOT is installed.
  • *2If the ambient temperature exceeds 40 ℃, the absolute humidity must not exceed 90% RH at 40 ℃.
  • *3Do not use or store the GOT under a pressure higher than the atmospheric pressure at altitude 0 m. Doing so may cause a malfunction. Air purging by applying pressure to the control panel may create clearance between the surface sheet and the touch panel. This may cause the touch panel to be not sensitive enough or the sheet to come off.
  • *4This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within the premises. Category II applies to equipment that is supplied with power from fixed facilities. The withstand surge voltage for the equipment with the rated voltage up to 300 V is 2500 V.
  • *5This indicates the occurrence rate of conductive material in an environment where a device is used. Pollution degree 2 indicates an environment where only non-conductive pollution occurs normally and a temporary conductivity caused by condensation shall be expected depending on the conditions.
  • *6When a protective cover for oil is mounted on the GOT, the maximum operating ambient temperature must be 5℃ lower than the one described in the general specifications.
  • *7The definitio